OPERATION Protocol Plus Owners Manual
44 Version 2
Copyright © 2010 by Despatch Industries.
All rights reserved. No part of the contents of this manual may be reproduced, copied or transmitted in any form or by any
means including graphic, electronic, or mechanical methods or photocopying, recording, or information storage and
retrieval systems without the written permission of Despatch Industries, unless for purchaser's personal use.
O
A profile must be created in the program page before trying to
run a profile number.
Table 14. Digital Input Parameters and Values.
Input 1
Input 2
Input 3
Profile Selected
ON
OFF
OFF
1
OFF
ON
OFF
2
ON
ON
OFF
3
OFF
OFF
ON
4
ON
OFF
ON
5
OFF
ON
ON
6
ON
ON
ON
7
OFF
OFF
OFF
none
To start the selected profile, set Inputs 1, 2 and 3. Then set Input 4 to ON.
To hold a profile, set Input 4 to OFF.
To stop a profile, set all inputs to OFF.
Figure 9. Digital Inputs.