Despatch P1400+ Temperature Controller Instrukcja Użytkownika Strona 21

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 110
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 20
15
4.9 Power Connections - Mains Powered Instruments
Mains powered instruments operate from a 100 to 240V (±10%) 50/60Hz supply. Power
consumption is 7.5VA. Connect the line voltage (live and neutral) as illustrated via a two-pole
isolating switch (preferably located near the equipment) and a 1amp anti-surge fuse. If the
instrument has relay outputs with contacts carrying mains voltage, it is recommended that the relay
contacts supply should be switched and fused in a similar manner, but should be separate from the
instruments mains supply.
Figure 10. Mains Power Connections
WARNING:
CHECK THE INFORMATION LABEL ON THE CASE TO DETERMINE THE CORRECT VOLTAGE
BEFORE CONNECTING TO A LIVE SUPPLY.
CAUTION:
This equipment is designed for installation in an enclosure that provides adequate
protection against electric shock
4.10 Power Connections - 24/48V AC/DC Powered Instruments
24/48V AD/DC powered instruments will operate from a 20 to 48V AC or 22 to 55V DC supply. AC
power consumption is 7.5VA max, DC power consumption is 5 watts max. Connection should be via
a two-pole isolating switch (preferably located near the equipment) and a 315mA slow-blow (anti-
surge type T) fuse.
Figure 11. 24/48V AC/DC Power Connections
13
14
L
N
13
14
_
+
Przeglądanie stron 20
1 2 ... 16 17 18 19 20 21 22 23 24 25 26 ... 109 110

Komentarze do niniejszej Instrukcji

Brak uwag