Despatch DES2000 Controller Instrukcja Użytkownika Strona 15

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
Przeglądanie stron 14
9
16. Press and hold the for three (3) seconds.
17. The display will read CtL. The SP LED will flash indicating that Operating
Parameter mode has been entered.
18. Press the until P appears on the display.
19. Press the or once to enter the parameter.
20. Press the to set the value to 5. The SP LED will flash indicating that the
setting is being changed.
21. Press the to enter the value.
22. Press and hold the for three (3) seconds to return to the operation mode.
23. The control now reads °F. Enter the desired setpoint.
Przeglądanie stron 14
1 2 ... 10 11 12 13 14 15 16 17 18 19

Komentarze do niniejszej Instrukcji

Brak uwag