Page 12 Despatch/Watlow 1500 Control Instruction Manual
ECOSPHERE/16000 Series Guarded Access Chart
Make a copy of this chart to document the Series 1500
Guarded Access for each program you use.
Program #_____ System _______ Programmer ________ Date__________
GA Code Ch Pmpt Parameter Typical ECOSPHERE Setting Your Settings
0000 C1 UP Ch-1 Upper Process Alarm 180
C1 LP Ch-1 Lower Process Alarm -75
C1 Ud Ch-1 Upper Deviation Alarm 538
C1 Ld Ch-1 Lower Deviation Alarm -538
C2 UP Ch-2 Upper Process Alarm 101
C2 LP Ch-2 Lower Process Alarm -001
C2 Ud Ch-2 Upper Deviation Alarm 101
C2 Ld Ch-2 Lower Deviation Alarm -101
0001 1 Pb Ch-1 Prop. Band 0009
1 RS Ch-1 Reset 0010
1 RT Ch-1 Rate 0000
1 Rb Ch-1 Rate Band 0001
1 CT Ch-1 Cycle Time 0003
1 db Ch-1 Dead Band 0001
1 CA Ch-1 Calibration Adjust. 0000
Dual
PID
1C Pb Ch-1 Prop. Band 0009
1C RS Ch-1 Reset 0002
1C RT Ch-1 Rate 0001
1C Rb Ch-1 Rate Band 0001
1C CT Ch-1 Cycle Time 0007
0002 2 Pb Ch-2 Prop. Band 0020
2 RS Ch-2 Reset 0010
2 RT Ch-2 Rate 0050
2 Rb Ch-2 Rate Band 0003
2 CT Ch-2 Cycle Time 0002
2 db Ch-2 Dead Band -0001
2 CA Ch-2 Calibration Adjust. 0000
Dual
PID
2C Pb Ch-2 Prop. Band 0020
2C RS Ch-2 Reset 0006
2C RT Ch-2 Rate 0001
2C Rb Ch-2 Rate Band -0001
2C CT Ch-2 Cycle Time 0005
0006 U1 Ch-1 Upper Set Point Limit 177
L1 Ch-1 Lower Set Point Limit -73
U2 Ch-2 Upper Set Point Limit 100
L2 Ch-2 Lower Set Point Limit 000
RC Recycle: ON = 1, OFF = 0 0
TT T-RH = 0000, T-T = 0001 0
Ad Address number RS-422 0
LC Keyboard Lock 0